Public address systems: paging, background music and announcements
It looks like the system isn't a fire alarm, so nobody quite owns it: the paging that half the building can't hear, the background music that drowns out the announcements, the microphone that hums.
A public address (PA) system that is not a fire voice alarm (paging, background music, announcements and sound reinforcement) is covered by BS 6259:2015. It is looked after the same way as a voice alarm: measured, recorded and compared with the last visit, with any repair quoted separately from the visit that found it.
Start the conversationOr call 01273 034 630.
Is my system a PA or a voice alarm?
What it is for decides. A system that broadcasts the evacuate message when the fire alarm operates is a voice alarm under BS 5839-8:2023, even if it plays music the rest of the day. A system for speech and music that is not connected to fire detection is a PA system under BS 6259:2015, including one that carries emergency messages of other kinds (BS 6259:2015, Clause 1). Many buildings have both on the same loudspeakers, and then each function follows its own standard. If you are not sure which you have, the panel and the cause-and-effect usually settle it on the first visit.
What does BS 6259 ask of a PA system in service?
- A weekly check, logged. A named responsible person makes sure the system is checked at least weekly, or before each use if it is used less often, and records tests, faults and complaints in the logbook (Clauses 12.1 and 13).
- Periodic inspection. A review of the logbook; a look for new partitions, changes of use or noise that affect the design; controls and indicators checked; and intelligibility and the signal-to-noise ratio re-checked with the building's normal equipment running (Clause 12.2).
- Emergency messages first. Where the system carries emergency messages, they take priority over everything else, and the arrangements are written into the site's emergency plan (Clause 5.2).
- A certificate for every change. After a modification, a new commissioning certificate from whoever did the work (Clauses 11 and 12.3).
The detail, clause by clause: BS 6259:2015, in our own words.
What a visit covers
The same discipline as a voice alarm visit, scaled to the system. Amplifiers, mixers and sources are checked against what they should deliver; loudspeaker circuits are measured and the readings kept, so next year's visit has something to compare with; microphones, leads and connectors, which fail more often than the electronics, are checked and remade where needed; zones and priorities are tested; and the report says what was found, what it means and what it would cost to put right. If you have taken the system over and there are no records, the first visit is the special inspection BS 6259 recommends for a new maintainer: the records reviewed, a maintenance plan built, and any area without coverage or with poor intelligibility reported (Clause 12.3.2).
Where this has been done
Brighton Centre. Safety sound and legacy infrastructure compliance for Brighton's principal conference and entertainment venue: a site-wide communications system installed in 2025 and designed to expand as areas are refurbished, and BS 6259 compliance across large-format spaces with high public footfall. ProAudium installed that system in 2025. The venue's own technical staff run events across its spaces on it, with annual maintenance and technical support from ProAudium.