Office buildings: the voice alarm has to keep up with every fit-out
It looks like the floors keep changing hands, and every new fit-out leaves you a little less sure the voice alarm still reaches every room.
In an office building or across a commercial office estate, the Public Address Voice Alarm (PAVA) is maintained for floors that are let, stripped out and fitted out again, so a maintenance visit has to show the system covers the building as it is now, not as it was commissioned.
What brings a building manager to this page?
A fit-out that put up new meeting rooms, and nobody checked whether there is a loudspeaker inside them. A tenant asking who is responsible for the voice alarm on their floor. A fire strategy built on phased evacuation, and a panel nobody on site is confident operating. A fire risk assessor or an insurer asking for records the last contractor never kept. A retender where the reports list visits, not readings.
Which standards apply to an office building?
The voice alarm follows BS 5839-8:2023. Where a building is designed for phased evacuation, BS 9999 expects the fire alarm to incorporate a voice alarm to BS 5839-8 (BS 9999:2017, Clauses 12.2.2 and 15.3), and adds that the degree of manual control should suit the risk and the staff available to use it.
BS 5839-8 uses offices among its own examples. An office building over 30 m high on phased evacuation appears as an example of a Type V2 and of a Type V3 system, and a high-rise office let to several tenants with variable occupancy and a staffed control room as an example of a Type V4 (commentary to Clause 4). Loudspeaker zone boundaries should coincide with fire detection zone boundaries (Clause 11.3), and a staircase that adjoins more than one zone is normally a zone of its own (Clause 11.5, Note 2).
Fit-outs are where most office systems drift. BS 5839-8 recommends servicing at intervals not exceeding six months, including a visual inspection for structural or occupancy changes that affect the design, which the maintainer reports to premises management (Clause 40.1). When the system itself changes, a modification certificate is generally necessary where, for example, more than 5 % of loudspeakers are added or removed or the number of emergency loudspeaker zones changes (Clause 41.3, Note 3). Like-for-like replacement is repair, not modification (Clause 41.2).
BS 5839-8 also places duties on the building. A single named member of premises management supervises the system and keeps its documentation (Clause 42), and the premises test it weekly and record the result in the logbook (Clauses 39 and 43). In a building let floor by floor, it helps to settle in writing which party that is before the next tenant fits out.
What does a maintenance visit have to prove in an office building?
That every room the last fit-out created can still hear the message. On Recommended and Comprehensive, every loudspeaker circuit is measured and compared with the year before, so drift is caught before it becomes a fault. Loudspeakers are checked for operation, orientation and condition, and changes since the last visit are recorded, so the building manager has what they need to decide what to commission, because the standard places that decision with premises management, not the maintainer.
ProAudium maintains voice alarm systems in commercial office estates across London and the South East, with testing and reporting quoted separately from any repair.
Which service does an office building need first?
Scheduled maintenance that keeps pace with the fit-outs: see the three maintenance levels. When a fit-out changes the zones or the loudspeaker count, the addition and its modification certificate are upgrades and additions. If the system came with the building and nobody is sure what it is, start with a site assessment.
What else is worth reading for an office building?
- The fault started after the works: what to check when a fit-out is followed by a fault.
- Twenty-one loudspeakers or one zone: when voice alarm work stops being a repair: where a fit-out tips into a modification and needs a certificate.
- Changing voice alarm maintainer? The drawings were never theirs to hand over: what a new building manager or maintainer should ask for.
- What a year of voice alarm maintenance should contain: the two services and 52 weekly tests, set out.
- Public address systems: paging and background music that are not part of the voice alarm, under BS 6259.
- BS 5839-8, in our own words: the clauses this page cites.