Standards
BS 6259:2015, in our own words
BS 6259:2015 is the British code of practice for the design, planning, installation, testing and maintenance of sound systems for speech, music and other signals: public address, paging, background music and sound reinforcement. It is the standard for a public address (PA) system that is not a fire voice alarm. It superseded the 1997 edition on 31 March 2015. It is a code of practice: it recommends. Counted on the published text, it uses "should" 178 times and "shall" not at all.
These are our explanations, in our own words, of the clauses that matter most for a PA system in service. We do not reproduce the standard's text: the clause numbers are there so you can check each one against your own copy. They support the published standard and the judgement of a competent technician, and replace neither.
The standard itself: BS 6259:2015 at BSI. Clause references checked against BS 6259:2015 on 10 October 2026.
Is my PA system under BS 6259 or BS 5839-8? Clause 1
It depends on what the system is for, not what it looks like. BS 6259 covers sound systems for speech, music and other signals, including systems that carry emergency messages but are not connected to a fire detection system (Clause 1). It does not apply to a voice alarm within BS 5839-8, to an emergency voice communication system within BS 5839-9, or to an emergency sound system within BS 7827, and it lists other exclusions such as cinema sound, home entertainment and audio conferencing. One set of loudspeakers can do both jobs: a system that plays background music all day and broadcasts the evacuate message when the fire alarm operates is a voice alarm for its fire function, and its everyday PA function sits under BS 6259.
Is BS 6259 a requirement?
A code of practice recommends. Its recommendations bind only when a contract, a specification or a licence calls them up, and Clause 4.1 says a purchaser who wants a compliant system should write the standard into the agreement for the installation, a modification or an extension. Without that, a departure from the code is still evidence of poor practice if anything is disputed later.
Clause 5.1: what category of system do you have?
BS 6259 sorts systems into three categories, so that the design and the tests match what the system is for. S1 puts speech intelligibility first, with naturalness secondary; it suits announcements and emergency messages in noisy or reverberant spaces. S2 is the most common: intelligible, natural speech and pleasant music where the acoustics are fairly good. S3 is the highest quality of reproduction, for a critically attentive audience in a space with very good acoustics. The "S" keeps these apart from the fire alarm and voice alarm classes. Paging and background music in shops and offices is usually S1 or S2.
Clause 5.2: emergency messages come first
Where a PA system carries emergency messages, its emergency operation should be written into the site's emergency plan, and emergency messages should take priority over every other function (Clause 5.2). A background music source that keeps playing over an emergency announcement is the failure this clause is there to prevent.
Clauses 4.7 and 4.8: what the system should achieve, in writing
The designer prepares a performance specification and agrees it with the client: it is what the system has to meet when it is commissioned (Clause 4.7). The tests of the completed installation are written down in advance too: intelligibility, judged both by listening and by measurement; installation quality; inputs, controls and priorities; documentation; zoning; and unwanted coverage and noise pollution, with what happens if the system fails them (Clause 4.8). If nobody can find the specification, nobody can say whether the system still meets it.
Clause 7.5 and Annex E: intelligibility
Intelligibility depends on the speech being loud enough and clear enough, and too much loudness makes it worse. The Speech Transmission Index (STI) is one objective measure, but no method is fully reliable on its own, so the code recommends a subjective assessment as well (Clause 7.5). Annex E gives example bands: 0.50 is the usual voice alarm target, and the bands from 0.38 down are described as not suitable for PA at all (Table E.1).
Clauses 7.6.2, 8.3 and Annex D: wiring
Microphone and other signal cables are Category 2 circuits under BS 7671 and should be kept apart from mains and other Category 1 cables (Clause 7.6.2); for microphone cables Annex D.3 gives at least 300 mm, or dedicated, compartmented trunking or conduit. Every circuit should be tested for continuity, and insulation resistance should be at least 2 MΩ between conductors, to earth and to the screen (Clause 8.3). Cables should not be supported by a suspended ceiling (Clause 8.2).
Clause 11: three certificates, not one
After design, installation and commissioning, a separate certificate is issued for each, and each stands on its own: one should not depend on another being issued. The client then completes an acceptance certificate, having checked that intelligible broadcasts are possible, that the drawings, instructions, certificates and logbook have been handed over, and that enough staff have been trained (Clause 11). After a modification, the client should ask for a new commissioning certificate from whoever did the work.
Clauses 12 and 13: keeping it working
A single named responsible person makes sure the system is checked at least weekly, or before each use if it is used less often than weekly, and that tests, faults and user complaints are recorded in the logbook (Clauses 12.1 and 13). Periodic inspection reviews the logbook, looks for changes to partitions, occupancy or noise that affect the design, checks controls and indicators, and re-checks intelligibility against the design minimum and the signal-to-noise ratio with the building's normal equipment running (Clause 12.2). A new maintainer should begin with a special inspection and a review of the records, and report any area without coverage or with unacceptable intelligibility (Clause 12.3.2).
Where these clauses are used
The weekly check, the periodic inspection and the logbook are the basis of how a PA system is maintained: public address systems. Where a PA system shares loudspeakers with a voice alarm, the voice alarm side follows BS 5839-8, and at a large venue BS 7827 decides which zones follow which standard.
Clause numbers refer to BS 6259:2015.