BS 5839-9:2021 is the British code of practice for the design, installation, commissioning and maintenance of emergency voice communication (EVC) systems: fixed, two-way voice communication between a master station and outstations around a building, for use in an emergency (Clause 3.4). In practice that means three things: fire telephones for the fire and rescue service, wardens and marshals; refuge intercoms, so that someone waiting in a disabled refuge can talk to the people managing the evacuation; and stewards' telephones at sports grounds. It was published on 31 August 2021 and superseded the 2011 edition. It is a code of practice: it recommends. Counted on the published text, it uses "should" 438 times and "shall" seven times, all seven in Annex C, which adapts type tests from BS EN 54-2.
These are our explanations, in our own words, of the clauses that matter most for an emergency voice communication system (EVCS) in service. We do not reproduce the standard's text: the clause numbers are there so you can check each one against your own copy. They support the published standard and the judgement of a competent technician, and replace neither.
The standard itself: BS 5839-9:2021 at BSI. Clause references checked against BS 5839-9:2021 on 11 October 2026.
Do I need an EVCS? Clause 1
BS 5839-9 does not decide that. It tells you how to design, install and look after a system once the fire strategy for the building says one is needed (Clause 1); whether a refuge or a fire telephone is needed is a question for the fire strategy and the design standards behind it, such as BS 9999. An EVCS is not normally the way a fire alarm is raised: that is the fire detection and alarm system under BS 5839-1. The standard also leaves out voice alarm, which is BS 5839-8, general-purpose intercoms and lift intercoms.
Is BS 5839-9 a requirement?
A code of practice recommends. Its recommendations bind only when a contract, a specification, a regulation or a safety-certificate condition calls them up. Where a design departs from a recommendation, the departure is a variation, which Clause 6 covers. The standard names the duty-holder as "premises management", and that is the term used here.
What changed in 2021
The principal changes from the 2011 edition: a third type of outstation for a refuge inside a firefighting lobby; systems with more than one master station, one of which is in control at any time; transmission paths across a campus of buildings; revised guidance on background noise; mains isolation brought into line with BS 5839-1; the siting and indicators of stewards' telephones; routine testing of devices on the system that are not EVC devices; and a battery calculation in Annex B that is now normative.
Clause 11: outstations
There are three types of outstation (Clause 11.1). Type A is a telephone handset, the fire telephone used by wardens, marshals and firefighters, and is coloured red. Type B is hands-free, with a call button, microphone and loudspeaker, for refuges, and is coloured green; where background noise in a refuge cannot be controlled, a Type A is used instead. Type C, new in 2021, serves a refuge inside a firefighting lobby: a hands-free unit with a handset behind a cover that takes over when it is lifted. Firefighting outstations are mounted 1.3 m to 1.4 m above the floor, and refuge outstations 0.9 m to 1.2 m, so that a wheelchair user can reach one (Clause 11.6 h) and j)). An outstation in a refuge should never be locked or otherwise secured against use (Clause 11.5 i)): the person who needs it may have no key.
Clause 12: the master station
Where there is more than one master station, one should be in control at a time. The master station should be near the fire alarm control panel, somewhere quiet enough to hold a conversation, with its controls behind access level 2. Everyone who might use the system should be trained, and the training repeated at least once a year.
Clause 13: power supplies and the standby battery
The mains supply should be a dedicated circuit, labelled so that nobody switches it off (Clause 13.1 f)). The standby battery should run the system for 24 h on standby and then 3 h in use; where an automatically starting generator serves the EVCS, that falls to 3 h on standby and 3 h in use (Clause 13.2 e)). The capacity is calculated by the method in Annex B.
Clause 14: cables
Where the fire and rescue service will use the system, its cables should have enhanced fire resistance. A system serving refuges only may use cables of standard or enhanced fire resistance.
Clauses 28 and 29: keeping it working
Every week, at least one outstation should be tested, rotating so that each is tested in turn; devices on the system that are not EVC devices should be tested weekly too, with all of them tested within 12 months (Clause 28.1 d)). A standby generator should be tested monthly, and vented batteries checked quarterly. Every six months the system should be inspected and serviced, working through the list in Clause 29.2 a) to i).
Clause 30: taking over, faults and changes
A new maintainer should start with a special inspection, which looks for seven named kinds of non-conformity (Clause 30.1 b)). Where a maintenance organisation looks after the system, it should normally attend a fault within eight hours of the call (Clause 30.2 a)). A modification should be certified by whoever made it (Clause 30.3 f)), and the system should be inspected and tested after a fire (Clause 30.4) and after it has been disconnected (Clause 30.5).
Clauses 31 and 32: who is responsible
Premises management should name a single person to look after the system, with enough authority to see that it is tested and serviced, and to make sure a call from a refuge is cancelled at the master station only once it is certain that nobody is in distress (Clause 31). Clause 32 lists the seven things the logbook should record.
What about the equipment itself?
BS 8893:2024, published on 15 March 2024, is a separate specification for EVC system components; BS 5839-9:2021 came first and does not refer to it. Cite BS 5839-9 for design, installation, commissioning and maintenance, and BS 8893 for whether a component conforms. BSI has a revision of BS 5839-9 under way (project 9026-13704) to take account of BS 8893 and BS 5839-8:2023; as at 10 October 2026 no draft or date had been published.
Where these clauses are used
Refuge call points and fire telephones are part of what we maintain: the systems we look after. If a refuge call point or fire telephone is not working now: the refuge call point isn't working. Where the same building has a voice alarm, that follows BS 5839-8.
Clause numbers refer to BS 5839-9:2021.